MVS20H3MF2L
| DIMENSIONS DRAWINGS |

| ASSEMBLY |


| PERFORMANCE CURVES |

THÔNG SỐ KĨ THUẬT
| MAIN |
| Range | EasyPact |
|---|---|
| Product name | MVS20H |
| Device short name | MVS20H |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3P 3d |
| [In] rated current | 2000 A at 40 °C |
| Network type | AC |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | H |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category B |
| Trip unit name | ET2I |
| Trip unit technology | Electronic |
| Trip unit rating | 2000 A |
| COMPLEMENTARY |
| Network frequency | 50/60 Hz |
|---|---|
| Control type | Manually operated |
| Mounting mode | Fixed |
| Mounting support |
Rail Base plate |
| Connection position |
Horizontal Vertical |
| Location of connection | Rear |
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 12 kV conforming to IEC 60947-2 |
| Circuit breaker CT rating | 2000 A |
| Breaking capacity | 65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity |
65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability |
20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2 |
| Electrical durability |
Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 |
| Connection pitch | 115 mm without spreader |
| Contact position indicator | Yes |
| [Icm] rated short-circuit making capacity | 143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current |
65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Trip unit protection functions | LI |
| Protection type |
Instantaneous short-circuit protection Overload protection (long time) |
| Fault indication |
Short-circuit Overload Internal fault |
| Long time pick-up adjustment type Ir | Adjustable 9 settings |
| Long time pick-up adjustment range | 0.4...1 x In |
| Long time delay adjustment type | Adjustable 9 settings |
| [tr] long-time delay adjustment range | 0.5…24 s at 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Instantaneous pick-up adjustment type Ii | Adjustable 9 settings |
| Instantaneous pick-up adjustment range | 1.5...10 x Ir |
| Zone selective interlocking ZSI | With |
| Current sensor rating range | 400/2000 A |
| Maximum breaking time | 25 ms |
| Maximum closing response time | 70 ms |
| Height | 352 mm |
| Width | 422 mm |
| Depth | 297 mm |
| Net weight | 40 kg |
| ENVIRONMENT |
| Standards | IEC 60947-2 |
|---|---|
| Product certifications |
GOST IEC CCC CCS |
| Pollution degree | 4 conforming to IEC 60664-1 |
| IP degree of protection | IP40 |
| Ambient air temperature for operation | -5…70 °C |
| Ambient air temperature for storage |
-40…85 °C without control unit -25…85 °C with control unit |
| PACKING UNITS |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 42.0 cm |
| Package 1 Width | 35.0 cm |
| Package 1 Length | 50.0 cm |
| Package 1 Weight | 45.667 kg |
Quý khách có nhu cầu đừng ngần ngại liên hệ cho chúng tôi theo số hotline :
HCM:
0981 817 642 (kinhdoanh@khovattucongnghiep.com)
0972 789 084 (kinhdoanh01@khovattucongnghiep.com)
Hà Nội: 0989 374 066 (sales@khovattucongnghiep.com)
Hoặc gửi e-mail yêu cầu chào giá cho số lượng (trả lời e-mail trong vòng 30p)
Tân Thành Đạt là đơn vị chuyên cung ứng vật tư cho nhà máy, nhà xưởng, công trình xây dựng…